520C Series
HART® and SIL 2 Compatible Universal Dual-input Head Mounted Temperature Transmitter
The 520C Series is a universal, isolated, dual-input head mounted temperature transmitter with additional voltage and resistance input. The 520C is approved for Non-Incendive use in Ex-Zone 2 and is Intrinsically Safe for use in Ex-Zone 0, 1 and 2. The transmitter is compatible with the HART® 6 protocol and SIL 2 according to IEC 61508-2.
Typical characteristics are high accuracy, stability and reliability combined with a robust housing.
TECHNICAL SPECIFICATIONS
- Universal dual-input for RTD and TC
- Input RTD: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 and Cu10
- Input TC: Type B, C, D, E, J, K, N, R, S, T
- Accuracy: ±0.05% of span
- Stability: ±0.01% of span/year
- Output: 4-20 mA, 20-4 mA or customized, HART® protocol
- HART® compliance: Fully compliant with HART® 6 protocol
- 50-point custom linearization capability
- Sensor backup with automatic switch-over to the other sensor
- Sensor drift monitoring
- Sensor isolation monitoring
- Sensor matching
- SIL 2 compatible according to IEC 61508-2
- Complies with NAMUR NE21, NE43, N53, NE89 and NE107
- EMC immunity according to Criteria A
- Integrated in Emerson AMS and Siemens PDM systems
- Galvanic isolation: 1500 VAC
- Measuring channels: 2 channels (redundancy)
- Sensor connection: 2-, 3-, 4-wire
- Power supply: 10-36 VDC (10-30 VDC Ex-version)
- Vibration: IEC 60068-2-6, 10 g
- Multiple configuration options